M-3520 Instruction Book
6–10
6.3
Automatic Calibration
The relay has been fully calibrated at the factory.
There is no need to recalibrate the unit prior to
installation. Recalibration is only necessary if a
component was changed.
For units with the optional M-3931 HMI:
8
WARNING: ALL RELAY FUNCTIONS AND
PROTECTION WILL BE INOPERATIVE WHILE THE
RELAY IS IN DIAGNOSTIC MODE
1.
Navigate to the
Auto Calibration
function
in the
Diagnostic Mode
menu. The
following is displayed:
AUTO CALIBRATION
clock led CAL factory
2.
Press
ENTER
. The following is displayed:
CONNECT REFERENCE INPUTS
PRESS ENTER TO CALIBRATE
3.
Connect all voltage inputs in parallel (V
A
=
V
B
=V
C
= V
2
) and apply 120.00 (±0.01) V
AC s0°. See Figure 6-7.
4.
Connect all current inputs in series
(I
A
=I
B
=I
C
=I
N
) and apply 5.00 (±0.01) Amps
s0°. See Figure 6-8. For 1 Amp CT models,
use 1.0 (±0.01) Amps s0°.
5.
Press
ENTER
to start calibration. This
process takes less than 5 seconds. The
unit will display the following while the
automatic calibration is in progress:
AUTO CALIBRATION
-WAIT-
6.
When the unit has completed calibration,
the following will be displayed:
AUTO CALIBRATION
-DONE-
7.
The calibration can be checked by using
the
Monitor Status
menu, see Section
3.3,
Checkout Status/Metering
.
For units without the optional M-3931 HMI:
It is possible to auto-calibrate Intertie Protection
Relays that are not equipped with the optional M-3931
HMI. The procedure is similar to HMI equipped units:
1.
Power down unit.
2.
Refer to Figure 6-8 and place unit in
calibrate mode by configuring the proper
dip switches.
3.
Connect all voltage inputs in parallel.
4.
Connect all current inputs in series.
5.
Power up unit.
6.
DIAG
LED will light when operation is
complete.
7.
Power down unit and return dip switches
to normal position.
35
36
Voltage
Input
120 VAC
s
0°
V
A
Hot
Neutral
V
B
V
C
39
40
37
38
V
G
41
42
43
44
V
2
Figure 6-7
Voltage Calibration Configuration
46
Current
Input
I
A
Polarity 47
48
I
B
49
50
I
C
51
52
I
G
53
5 Amps
s
0
o
Figure 6-8
Current Calibration Configuration
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...