Overview
PS2001-2410-0000 | Power supply 24V, 10A, 1 phase, Extra Power
• AC 100-240V wide-range input
• Efficiency of up to 95.2%
• Excellent part-load efficiency
• 120% peak power, 288W
• Safe hiccup overload mode
• Precise triggering of fuses through high overload / peak current
• Active Power Factor Correction (PFC)
• Minimum inrush current surge
• Full output between -25°C and +60°C
• DC-OK relay contact
The power supply PS2001-2410-0000 is a single-phase, 24 V DC power supply with an output current of 10
A and an output power of 240 W.
On the input side, the device features a wide-range input, Active Power Factor Correction (PFC) and inrush
current limiting.
The output operates according to the UI characteristic curve and switches to the safe hiccup mode in case of
overload/short-circuit. The PS2001-2410-0000 features extra power with a continuous maximum output
power of 120% and can precisely trigger fuses with a short peak current.
The power supply unit is part of the PS2000 family and has a width of 39 mm. A DC-OK LED and a potential-
free relay contact monitor the status of the output voltage. Thanks to approvals for the process industry
(ATEX/IECEx), shipbuilding (DNV/GL) and the semiconductor industry (SEMI-F47), the power supply unit
can be used in a wide range of applications.
Overview of technical data
*)
Overview of technical data
PS2001-2410-0000
Output voltage
DC 24V (nominal factory setting 24.1V)
Adjustment range
24 - 28V
Output current
12.0-10.3A (amb. below +45°C)
10.0-8.6A (amb. at +60°C)
7.5-6.5A (amb. at +70°C)
Linear load reduction b45°C and +70°C
Input voltage AC
AC 100-240V -15%/+10%
Mains frequency
50-60Hz ±6%
Input current AC
2.15 / 1.13A at 120 / 230Vac
Input voltage DC
DC 110-150V ±20%
Efficiency
93.6 / 95.2% at 120 / 230Vac
Temperature range
-25°C to +70°C
Size (W x H x D)
39 x 124 x 117mm (without DIN rail)
Weight
600 g
Approvals/markings
CE
cULus
Class I Div2
ATEX
IECEx
DNV/GL
SEMI F47
EAC
*) All values typical for 24V, 10A, 230Vac, 50Hz, +25°C ambient temperature and after a warm-up period of five minutes, unless other-