Operation
EL6910
55
Version: 1.8.0
Group Port Direction
Description
Err Ack
IN
Error Acknowledge for resetting errors within the group
- Signal must be linked with a standard variable
Run/Stop
IN
1 - Run; 0 – Stop
- Signal must be linked with a standard variable
Module
Fault
IN
Input for an error output of another module that is connected, e.g.
EK1960
Com Err
OUT
Communication error in one of the connections
FB Err
OUT
Error at one of the FBs used
Out Err
OUT
not used
Other Err
OUT
ModuleFault OR AnalogValueFault OR WaitComTimeoutFault
Com Startup OUT
At least one of the connections of this group is in startup
FB Deactive OUT
The group was deactivated. (See also chapter
)
FB Run
OUT
FBs of the TwinSAFE group are processed
In Run
OUT
TwinSAFE group is in RUN state
Group State
Value
Status
Description
1
RUN
Input RUN=1, no error in the group, and all connections have started up
without error
2
STOP
Input RUN = 0
4
ERROR
Group is in error, see Diagnostic information
5
RESET
After an error has occurred, all errors have been rectified and the Err Ack
signal is 1
6
START
The group remains in this state as long as not all connections have
started up after the start of the group (RUN=1)
7
STOPERROR
When the group is started or initialized, it assumes the STOPERROR
status if the TwinSAFE connections are assigned to the group.
The group switches from STOPERROR state into ERROR state if the
Run input is TRUE.
16
DEACTIVE
Group was deactivated via customizing
17
WAITCOMERROR
This state is set when the customizing function “Passivate” is selected
and the system waits for ComError of the group
Group Diag
Value
Status
Description
0
-
No error
1
FBERROR
at least one FB is in ERROR state
2
COMERROR
at least one connection is faulty
3
MODULEERROR
the input ModuleFault is 1
4
CMPERROR
On startup, at least one analog FB input deviates from the last saved
value (Power-On Analog Value Check Error)
5
DEACTIVATE
ERROR
In "passivate manual control unit" mode the timeout has elapsed while
waiting for the COM error
6
RESTARTERROR
The TwinSAFE Logic program was restarted because the EtherCAT
connection was restarted or a user logged in without reloading the
TwinSAFE Logic program (or parts of it).
Summary of Contents for TwinSAFE EL6910
Page 1: ...Operation Manual for EL6910 TwinSAFE Logic Terminal 1 8 0 2019 01 09 Version Date...
Page 2: ......
Page 69: ...Operation EL6910 69 Version 1 8 0 Fig 73 The Safety Project Online View tab...
Page 136: ...Appendix EL6910 136 Version 1 8 0 5 2 Certificates...
Page 137: ...Appendix EL6910 137 Version 1 8 0...