Technical data, mounting, wiring
PS3011-2440-0000
14
Version: 1.0
2)
Hiccup mode
In the event of a severe overload, the power supply provides continuous output current for 4 s. The output is
then switched off for about 17 seconds before a new switch-on attempt is automatically made. This cycle is
repeated as long as the overload persists. If the overload persists, the output current is restored for 2 to
4 seconds (depending on the overload), followed by another recovery time of 17 seconds. After the overload
has been rectified, the device will operate normally. See Fig.
Short circuit at output, hiccup mode, typ.
During the pause time, a small residual voltage and a residual current are applied to the output.
3)
The discharge current of the output capacitors is not included.
Fig. 4: Output voltage over output current typ. in "Single Use" mode; output voltage over output current typ.
in "Parallel Use" mode,
Fig. 5: Short circuit at output, hiccup mode, typ.; Dynamic overcurrent capacity, typ.
Fig. 6: Bonus time over output power; Extra power recovery time
Extra power is available as soon as the power is turned on and after an output short-circuit or output
overload.