Technical data, mounting, wiring
PS1111-2403-0002
22
Version: 1.0
3.14
Protective functions and safety features
Protective functions and safety features
Insulation resistance
> 500MOhm
Under given conditions between input and output, measured with
500Vdc
Output overvoltage protection
Typ. 30.5Vdc
Max. 32Vdc
In the event of an internal power supply fault, a redundant circuit limits
the maximum output voltage to 32V. The output switches off. To at-
tempt a restart, turn off the input voltage for at least 90 seconds.
Protection class
II
According to EN/IEC 61140
Protection class
IP 20
According to EN/IEC 60529
Overtemperature protection
-
.
Protection against input transients
MOV (metal oxide
varistor)
chapter
Input fuse
included
Non-replaceable slow-blow fuse with high load capacity
Leakage current
Typ. 50µA / 120µA
At 100Vac, 50Hz, TN, TT / IT network
Typ. 75µA / 170µA
At 120Vac, 60Hz, TN, TT / IT network
Typ. 130µA / 270µA
At 230Vac, 50Hz, TN, TT / IT network
Max. 80µA / 190µA
At 110Vac, 50Hz, TN, TT / IT network
Max. 120µA / 270µA
At 132Vac, 60Hz, TN, TT / IT network
Max. 210µA / 400µA
At 264Vac, 50Hz, TN, TT / IT network