General
Number of Bus Terminals per Fieldbus Coupler
with BKxx20 or BKxx50 fieldbus coupler: max. 255
with Fieldbus Couplers BKxx00 or BKxx10: max. 64
Number of bytes per Fieldbus Coupler
limited by Fieldbus Coupler and Fieldbus Limit (see documentation for the Field-
bus Coupler being used)
Increase in runtime due to K-bus extension
negligible (see runtime calculation in the documentation for the Fieldbus Coupler
used)
Length of cable between 2 terminal blocks
max. 5 m
Total length of cable (from KL9020 to the last
KL9050)
max. 155 m (31 x 5 m)
Topology
Bus structure
Technical Data
End Terminal with RJ45 socket for K-Bus extension
Fieldbus
independent
Number of KL9020 per Fieldbus Coupler
1
Configuration
automatic
Current consumption from the K-bus
typically 70 mA
Dielectric strength
500 V (shielding, base plate / K-bus)
Permissible ambient temperature range during oper-
ation
0 °C ... + 55 °C
Permissible ambient temperature range during stor-
age
-25 °C ... + 85 °C
Permissible relative air humidity
95 %, no condensation
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Weight
approx. 45 g
Dimensions (W x H x D)
approx. 26 mm x 100 mm x 70 mm
on 35 mm mounting rail conforms to EN 60715
Installation position
variable
Protection class
IP20
Approvals
CE, UL,
Technical Data
K-Bus Extension Coupler Terminal
Number of Bus Terminals per KL9050
max. 64
Number of KL9050 per Fieldbus Coupler
max. 31
Configuration
via switch
Supply voltage
24 V
DC
(-15%/+20%)
Current consumption (via Terminals V
k
24V, V
k
0V)
maximum 200 mA
Calculation: 70 mA + (K-bus current of the terminal block) / 4
Starting current
2.5 x nominal current
K-bus power supply (for Bus Terminals)
maximum 400 mA
Power contacts voltage
maximum 30 V
DC
Power contact current load
10 A max. (short-circuit 125 A)
Dielectric strength
500 V (power contact/supply voltage/fieldbus)
Permissible ambient temperature range during oper-
ation
0 °C ... + 55 °C
Permissible ambient temperature range during stor-
age
-25 °C ... + 85 °C
Permissible relative air humidity
95 %, no condensation
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Weight
approx. 75 g
Dimensions (W x H x D)
approx. 24.5 mm x 100 mm x 70 mm
on 35 mm mounting rail conforms to EN 60715
Installation position
variable
Protection class
IP20
Approvals
CE, UL,