Programming in TwinCAT
KL85xx und KL9309
60
Version: 2.1.0
The LEDs flash green if the automatic switch is set to "man" and the respective output is TRUE (set by the
three-step switch).
This functionality can be disabled with the variable
byDisCh
. The LEDs can then be set from the PLC.
4.5.3
Standard function LED KL8528
The LEDs light up steadily yellow if the switch is set to
auto
and the output is FALSE.
The LEDs light up steadily green if the switch is set to
auto
and the output is TRUE (set by the PLC).
The LEDs flash yellow if the automatic switch is set to
off
. The respective output is then FALSE (even if it is
set by the PLC).
The LEDs flash green if the automatic switch is set to
man
. The respective output is then TRUE.
This functionality can be disabled with the variable
byDisCh
. The LEDs can then be set from the PLC.
4.5.4
Standard function LED KL8548
The LEDs are off if the switch is set to
auto
. The bar graph indicates the PLC value.
The LEDs light up steadily if the switch is set to
man
. The bar graph indicates the potentiometer value.
This functionality cannot be disabled.
4.5.5
Bar graph display mode - KL8548
Fig. 35: KL8548 - Bar graph display mode
The KL8548 offers two bar graph display modes for the analog values.
In full scale mode the current analog value is shown as a full bar.
In ECO mode the analog value is shown with one LED only.