EnOcean
KL6581 and KL6583
26
Version: 2.0.0
4.2
Range planning
Please follow the recommendations of the EnOcean Alliance (see
) when placing the
EnOcean devices. Adherence to the recommendations is conducive to an optimum range and high noise
immunity.
Attenuation of different materials
Material
Attenuation
Wood, plaster, uncoated glass (without metal)
0...10 %
Brick, chipboard
5...35 %
Concrete with iron reinforcement
10...90 %
Metal, aluminum cladding
90..100 %
Range
Material
Range
Line of sight
Typically 30 m in corridors, up to 100 m in halls
Plasterboard walls/wood
Typically 30 m, through max. 5 walls
Brick walls/aerated concrete
Typically 20 m, through max. 3 walls
Reinforced concrete walls/ceilings
Typically 10 m, through max. 1 wall/ceiling
Placement of the KL6583 module
The KL6583 module contains transmitter, receiver and antenna.
Distances
The distance to a reinforced concrete ceiling should be at least 50 cm and to a wall 10 cm.
Do not attach or screw the KL6583 module to a metal plate!
Environmental conditions
Furthermore, the environmental conditions are to be adhered to:
• Maximum air humidity 95% no condensation
• Ambient temperature 0...55 °C
Summary of Contents for KL6581
Page 2: ......
Page 4: ...Table of contents KL6581 and KL6583 4 Version 2 0 0...