KL6301-0000

21

Version: 3.0.0

4

EIB

4.1

Function of the KL6301

Operation of the EIB Bus Terminal requires function blocks that are available for downloading from within
this documentation.

From firmware version B1 and library version V3.000.000 there are three different modes that can be
activated in the KL6301 function block.

Mode 0: 4 filters, each with 64 group entries (compatible with firmware B0 )

Mode 1: 8 filters, each with 32 group entries

Mode 100: Monitor function (all group address telegrams can be received, the KL6301 sends no ACK).
Sending is disabled in this mode.

Mode 1 and 100

Modes 1 and 100 can only be used with the basic function blocks from the TcKL6301 library.

Sending

The KL6301 sends data individually. This means that a Data variable sent to the KL6301 is sent to the EIB
network individually. Subsequent EIB data can only be transferred to the KL6301 after a successful transfer.
Two types of EIB telegrams can be sent:

• WRITE_GROUP for writing data to other EIB devices

• READ_GROUP_REQ for requesting data from other EIB devices

Receiving

The KL6301 has a maximum of 8 filter addresses. These filters filter the EIB group addresses. Only EIB
telegrams entered in the filter are visible in the process image and are acknowledged.

A filter may contain up to 64 group addresses. With 4 filters multiplied with 64 entries a total of 256 group
addresses are available. With 8 filters multiplied with 32 entries a total of 256 group addresses are available.
The system is configured via a function block. The group addresses are loaded and are immediately active
when the Bus Terminal is initialized.

At least one filter has to be parameterized. The type of data is irrelevant for the filter setting.

Monitor function

No filters must be set if mode 100 is enabled. The filters EIB_GROUP_FILTER are simply left empty and not
written.

Summary of Contents for KL6301-0000

Page 1: ...Documentation KL6301 0000 EIB KNX Bus Terminal 3 0 0 2019 05 24 Version Date...

Page 2: ......

Page 3: ...echnical data 10 3 Mounting and wiring 11 3 1 Installation on mounting rails 11 3 2 Connection 13 3 2 1 Connection system 13 3 2 2 Wiring 15 3 3 Connection 17 3 4 Installation instructions for enhance...

Page 4: ...Table of Contents KL6301 0000 4 Version 3 0 0...

Page 5: ...ata diagrams and descriptions in this documentation Trademarks Beckhoff TwinCAT EtherCAT EtherCAT P Safety over EtherCAT TwinSAFE XFC and XTS are registered trademarks of and licensed by Beckhoff Auto...

Page 6: ...trained specialists in control automation and drive engineering who are familiar with the applicable national standards Description of instructions In this documentation the following instructions ar...

Page 7: ...can also be used with firmware version B0 In that case however only the 4 filters with 64 entries each are possible 1 2 0 Mounting description expanded 1 1 0 New output variable in receive function bl...

Page 8: ...inCAT function blocks IEC61131 3 Software required for use of the KL6301 1 An ETS tool for linking the data and commissioning the other EIB KNX devices 2 TwinCAT PLC and an appropriate library to comm...

Page 9: ...or strongly K bus communication OK No K Bus communication K Bus communication Set green No significance EIB TXD green Goes out briefly when an EIB telegram is sent EIB RXD POWER green Goes out briefly...

Page 10: ...Output 24 bytes data input 24 bytes data Weight approx 85 g Dimensions W x H x D approx 12 mm x 100 mm x 70 mm Mounting 11 on 35 mm mounting rail conforms to EN 60715 Permissible ambient temperature r...

Page 11: ...the fieldbus coupler Join the compo nents with tongue and groove and push the terminals against the mounting rail until the lock clicks onto the mounting rail If the terminals are clipped onto the mou...

Page 12: ...ponents The six spring contacts of the K Bus E Bus deal with the transfer of the data and the supply of the Bus Terminal electronics The power contacts deal with the supply for the field electronics a...

Page 13: ...10 mm from the group of terminals WARNING Risk of electric shock The PE power contact must not be used for other potentials 3 2 Connection 3 2 1 Connection system WARNING Risk of electric shock and da...

Page 14: ...minates the risk of wires being mixed up The familiar dimensions of the terminal only had to be changed slightly The new connector adds about 3 mm The maximum height of the terminal remains unchanged...

Page 15: ...disassembly or wiring of the Bus Terminals Terminals for standard wiring ELxxxx KLxxxx and for pluggable wiring ESxxxx KSxxxx Fig 9 Connecting a cable on a terminal point Up to eight terminal points...

Page 16: ...he HD Terminals are connected without tools for single wire conductors using the direct plug in technique i e after stripping the wire is simply plugged into the terminal point The cables are released...

Page 17: ...No Connection for Set 1 reserved EIB 2 EIB plus red internally connected with terminal point 6 EIB 3 EIB minus grey internally connected with terminal point 7 Shield 4 Shield internally connected wit...

Page 18: ...cal load capacity the following additional installation instructions apply The enhanced mechanical load capacity is valid for all permissible installation positions Use a mounting rail according to EN...

Page 19: ...against the rated operating voltage being exceeded by more than 40 due to short term interference voltages The individual terminals may only be unplugged or removed from the Bus Terminal system if the...

Page 20: ...the Beckhoff terminal systems in potentially explosive ar eas ATEX Pay also attention to the continuative documentation Notes about operation of the Beckhoff terminal systems in potentially explosive...

Page 21: ...sequent EIB data can only be transferred to the KL6301 after a successful transfer Two types of EIB telegrams can be sent WRITE_GROUP for writing data to other EIB devices READ_GROUP_REQ for requestin...

Page 22: ...rogramming KL6301 0000 22 Version 3 0 0 5 Programming 5 1 TwinCAT libraries Software documentation in the Beckhoff Information System TwinCAT 2 TwinCAT 2 PLC Lib EIB TwinCAT 3 TwinCAT 3 PLC Lib Tc2_EI...

Page 23: ...off components there Beckhoff Headquarters Beckhoff Automation GmbH Co KG Huelshorstweg 20 33415 Verl Germany Phone 49 0 5246 963 0 Fax 49 0 5246 963 198 e mail info beckhoff com Beckhoff Support Supp...

Page 24: ...2 KL6301 Diagnostic LEDs 9 Fig 3 Attaching on mounting rail 11 Fig 4 Disassembling of terminal 12 Fig 5 Power contact on left side 13 Fig 6 Standard wiring 14 Fig 7 Pluggable wiring 14 Fig 8 High Dens...

Reviews: