Mounting and wiring
KL4414, KL4418, KL4424, KL4428
22
Version: 3.0.0
See the following table for the suitable wire size width.
Terminal housing
ELxxxx, KLxxxx
ESxxxx, KSxxxx
Wire size width (single core wires)
0.08 ... 2.5 mm
2
0.08 ... 2.5 mm
2
Wire size width (fine-wire conductors)
0.08 ... 2.5 mm
2
0,08 ... 2.5 mm
2
Wire size width (conductors with a wire end sleeve)
0.14 ... 1.5 mm
2
0.14 ... 1.5 mm
2
Wire stripping length
8 ... 9 mm
9 ... 10 mm
High Density Terminals (
) with 16 terminal points
The conductors of the HD Terminals are connected without tools for single-wire conductors using the direct
plug-in technique, i.e. after stripping the wire is simply plugged into the terminal point. The cables are
released, as usual, using the contact release with the aid of a screwdriver. See the following table for the
suitable wire size width.
Terminal housing
High Density Housing
Wire size width (single core wires)
0.08 ... 1.5 mm
2
Wire size width (fine-wire conductors)
0.25 ... 1.5 mm
2
Wire size width (conductors with a wire end sleeve)
0.14 ... 0.75 mm
2
Wire size width (ultrasonically “bonded" conductors)
only 1.5 mm
2
Wire stripping length
8 ... 9 mm
5.4.3
Shielding
Note
Shielding
Encoder, analog sensors and actors should always be connected with shielded, twisted
paired wires.