Mounting and wiring
KL4132
19
Version: 3.0
3.5
KL4132 - connection and LED description
WARNING
Risk of injury through electric shock and damage to the device!
Bring the Bus Terminals system into a safe, de-energized state before starting mounting,
disassembly or wiring of the Bus Terminals!
Fig. 10: KL4132 - connection and LEDs
Connection KL4132
Terminal point
No.
Comment
Output1
1
+ Output 1
n.c.
2
Not used
GND
3
Internal ground (internally connected to terminal point 7)
Shield
4
PE contact (internally connected to terminal point 8)
Output2
5
+ Output 2
n.c.
6
Not used
GND
7
Internal ground (internally connected to terminal point 3)
Shield
8
PE contact (internally connected to terminal point 4)
LED description KL4132
LED
Color
Description
Run1 LED
Run2 LED
green
On:
Normal operation
Off:
Watchdog timer overflow has occurred. If no process data is transmitted to the bus cou-
pler for 100 ms, the green LEDs go out. The output assumes a user-specified voltage
(see
Summary of Contents for KL4132