Access from the user program
KL320x
37
Version: 4.4
Default mapping for:
PROFIBUS, Interbus
Conditions
Word offset
High byte
Low byte
Complete evaluation: no
Motorola format: ja
Word alignment: any
0
Ch0 D0
Ch0 D1
1
Ch1 D0
Ch1 D1
2
Ch2 D0
Ch2 D1
3
Ch3 D0
Ch3 D1
Conditions
Word offset
High byte
Low byte
Complete evaluation: yes
Motorola format: no
Word alignment: no
0
Ch0 D0
Ch0 CB/SB
1
Ch1 CB/SB
Ch0 D1
2
Ch1 D1
Ch1 D0
3
Ch2 D0
Ch2 CB/SB
4
Ch3 CB/SB
Ch2 D1
5
Ch3 D1
Ch3 D0
Conditions
Word offset
High byte
Low byte
Complete evaluation: yes
Motorola format: yes
Word alignment: no
0
Ch0 D1
Ch0 CB/SB
1
Ch1 CB/SB
Ch0 D0
2
Ch1 D0
Ch1 D1
3
Ch2 D1
Ch2 CB/SB
4
Ch3 CB/SB
Ch2 D0
5
Ch3 D0
Ch3 D1
Default mapping for:
Lightbus, EtherCAT, Ethernet and Bus Terminal Controller (BCxxxx, BXxxxx)
Conditions
Word offset
High byte
Low byte
Complete evaluation: yes
Motorola format: no
Word alignment: yes
0
res.
Ch0 CB/SB
1
Ch0 D1
Ch0 D0
2
res.
Ch1 CB/SB
3
Ch1 D1
Ch1 D0
Conditions
Word offset
High byte
Low byte
Complete evaluation: yes
Motorola format: yes
Word alignment: yes
0
res.
Ch0 CB/SB
1
Ch0 D0
Ch0 D1
2
res.
Ch1 CB/SB
3
Ch1 D0
Ch1 D1