Product overview
KL320x
15
Version: 4.4
2.2
Technical data
Technical data - KL3201, KL3202, KL3204, KL3204-0030
Technical data
KL3201
KL3202
KL3204-0000
KL3204-0030
Number of inputs
1
2
4
Power supply
via the K-bus
Sensor types
PT100, PT200, PT500, PT1000, Ni100, Ni120, Ni1000
resistance measurement (e.g. potentiometer connection)
NTC (10 kΩ)
Connection technology
2 or 3-wire (pre-set to 3-wire)
2-wire
Temperature range
-200°C ... +850°C (PT sensors); -60°C ... +250°C (Ni sensors)
Resolution
0.1°C per digit (measuring range 10 to 5000 Ω: 0.5°C per digit)
Electrical isolation
500 V (K-bus/signal voltage)
Conversion time
~ 200 ms
~ 250 ms
Measuring current
typically 0.5 mA
typically
<0.5 mA
Measuring error (total
meas. range)
< ± 1°C
< ± 1 C (at 0°C ... +55°C)
< ± 1.5% (when the extended temperature range is used)
Bit width in process image
Input: 1 x 16 bit
data
(1 x 8 bit Control/
Status optional)
Input: 2 x 16 bit data
(2 x 8 bit Control/
Status optional)
Input: 4 x 16 bit data
(4 x 8 bit Control/ Status optional)
Current consumption from
K-bus
typically 60 mA
Configuration
no address setting, configuration via bus coupler or controller
Special features
Wiring fail indication
Weight
approx. 70 g
Permissible ambient
temperature range
(operation)
0°C ... +55°C
-25°C ... +60°C in operation (extended
temperature range)
0°C ... +55°C
Permissible ambient
temperature range
(storage)
-25°C ... +85°C
-40°C ... +85°C
-25°C ... +85°C
Relative humidity
95%, no condensation
Vibration / shock resistance conforms to EN 60068-2-6 / EN 60068-2-27,
see also
installation instructions for enhanced mechanical
conforms to EN
60068-2-6 / EN
60068-2-27
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Installation position
variable
Protection class
IP20
Approvals
CE,
cULus,
(standard
temperature
range),
GL
CE,
cULus,
(extended temperature
range),
GL
CE