Mounting and wiring
KL26xx/KS26xx
35
Version: 2.5.0
3.3.6
KL/KS2631 – connection and LEDs
WARNING
Risk of injury through electric shock and damage to the device!
Bring the Bus Terminal system into a safe, de-energized state before starting mounting, disassembly or
wiring of the Bus Terminals!
NOTE
Risk of device damage!
Note that the use of potential separation terminals (e.g., KL9080) is necessary when planning the Bus Ter-
minal system with different potentials on the power contacts (e.g., 24 V
DC
and 230 V
AC
)!
Fig. 20: KL2631-0000 – connection and LEDs
KL/KS2631-0000 - connection
Terminal point
Description
Name
No.
Output 1
1
Output 1 (internally connected to terminal point 5)
400 V
2
400 V (internally connected to terminal point 6 and power contact 400 V)
N
3
N (internally connected to terminal point 7 and power contact N)
PE
4
PE (internally connected to terminal point 8 and power contact PE)
Output 1
5
Output 1 (internally connected to terminal point 1)
400 V
6
400 V (internally connected to terminal point 2 and power contact 400 V)
N
7
N (internally connected to terminal point 3 and power contact N)
PE
8
PE (internally connected to terminal point 4 and power contact PE)
KL/KS2631-0000 – LED displays
LED
Color State
Meaning
Signal LED 1
green off
Signal voltage "0"
on
Signal voltage "1"