FC310x as master
FC3101 and FC3102
36
Version: 3.0
3.6.5
S5-FDL Communication
FDL-AGAG communication is possible with S5 controllers or with other PROFIBUS FDL devices. The
following specifications apply here to the PROFIBUS SAPs:
FC310x sends
SDA request with DSAP = station a 1 of the FC310x and SSAP = station a 1 of the other
FDL device. Data corresponds to the data length passed with the ADS write. The SDA telegram is only sent
when there is a call to ADS write:
ADS-Write parameters
Meaning
Net-ID
Net-ID of the master (see the device's
tab)
Port
station address of the other FDL device
IndexGroup
0x01000000
IndexOffset
0
Length
Length of the data that is to be written
Data
In request: data that is to be written
Other FDL device sends:
SDA request with DSAP = station a 1 of the other FDL device and SSAP = station a 1 of
the FC310X. Data corresponds to the data length set at the other FDL device. The FC310x temporarily
stores the received data which can be read by ADS read:
ADS-Read parameters
Meaning
Net-ID
Net-ID of the master (see the device's
tab)
Port
station address of the other FDL device
IndexGroup
0x01000000
IndexOffset
0
Length
Length of the received data
Data
In response: received data. There is a receive counter at the end of the received
data that is incremented with every reception
ADS-Read parameters
Meaning
Net-ID
Net-ID of the master (see the device's
tab)
Port
station address of the other FDL device
IndexGroup
0x04000000
IndexOffset
Station address of the other FDL device * 2
Length
2
Data
In response: receive counter, incremented with each reception