Parameterization and commissioning
EL6752
81
Version: 2.1
Index F101 Network status
Index (hex) Name
Meaning
Data type
Flags
Default
F101:0
Network status
Max. Subindex
UINT8
RO
0x11 (17
dec
)
F101:01
Device status
0: RUN MODE
1: IDLE MODE
2: Duplicate MacId Check failed, MAC ID used
3: Status: Selftest
4: Status: Standby
5: Status:Major Recoverable Fault
6: Status:Minor Recoverable Fault
7: DeviceNet Voltage Error
8: DeviceNet Access Error
UINT8
RO
0x00 (0
dec
)
F101:09
CAN BUS-OFF
CAN controller of the EL6752-0010 is in state bus-off
BOOLEAN
RO
0x00 (0
dec
)
F101:0A
CAN warning limit
CAN controller of the EL6752-0010 has exceeded the
warning limit
BOOLEAN
RO
0x00 (0
dec
)
F101:0B
CAN Overrun
CAN controller of the EL6752-0010 is in state bus-off
BOOLEAN
RO
0x00 (0
dec
)
F101:11
CAN BUS load
CAN bus load 0 - 100 %
UINT16
RO
0x0000 (0
dez
)
Index F800 bus parameter set
Index (hex) Name
Meaning
Data type
Flags
Default
F800:0
Bus Parameter set
Max. Subindex
UINT8
RW
0x08 (8
dec
)
F800:01
MAC ID
Device address of the DeviceNet device (see DeviceNet
specification)
UINT16
RW
0x0000 (0
dec
)
F800:03
Product Name
Product name of the DeviceNet device (see DeviceNet
specification)
OCTET-
STRING[32]
RW
{0}
F800:04
DeviceType
Device type of the DeviceNet device (see DeviceNet
specification)
UINT16
RW
0x0000 (0
dec
)
F800:05
Vendor ID
Manufacturer ID of the DeviceNet device (see DeviceNet
specification)
UINT16
RW
0x0000 (0
dec
)
F800:06
Product Code
Product code of the DeviceNet device (see DeviceNet
specification)
UINT16
RW
0x0000 (0
dec
)
F800:07
Revision Number
Version number of the DeviceNet device (see DeviceNet
specification)
UINT16
RW
0x0000 (0
dec
)
F800:08
Serial Number
Serial number of the DeviceNet device (see DeviceNet
specification)
UINT32
RW
0x00350000
(3473408
dec
)
F800:09
Baud rate
DeviceNet Baud Rate
UINT16
RW
0x0100
(256
dec
)