IO-Link basics
EPI4xxx, ERI4xxx
16
Version: 1.6
3.2
Establishment of IO Link communication
The establishment of the IO-Link communication is illustrated in Fig.
Establishment of IO-Link
communication.
This illustrates in particular the sequence when
port.
Fig. 2: Establishment of IO Link communication
• If an IO-Link device is connected to a master port, the master attempts to establish communication. A
defined signal level, the
wake-up pulse
, signals to the device that UART bytes are to be sent from now
on.
From this point on, all data will be interpreted by the IO-Link device as UART bytes.
• The master runs through all
, starting with the fastest baud rate
(COM3 = 230 kbaud). A successful connection has been established when the slave responds to the
wake-up pulse.
• First of all the master reads the
basic parameters
(Vendor ID, Device ID, process data length,
telegram type and cycle time) and compares them with the existing configuration.
• If no connection could be established to the device, or if the saved parameters differ from those read,
the corresponding error is output.
• If the saved parameters differ from those read, the IO-Link device changes to the PREOP state.
If the IO-Link device specification is V1.1, the
is now executed. If the IO-Link
device specification is V1.0, this step is omitted and the device changes directly to OP.
• Finally the cycle time is written and the device changes to OP. After that the master cyclically
exchanges data with the device.
Summary of Contents for EPI4 Series
Page 2: ......
Page 51: ...Commissioning and configuration EPI4xxx ERI4xxx 51 Version 1 6 Fig 39 Store parameters ...
Page 81: ......