Commissioning/configuration of IO-Link master/device
EPI3xxx, ERI3xxx
62
Version: 1.2
Control/status word
Status word
The status word (SW) is located in the input process image, and is transmitted from terminal to the controller.
Bit
SW.15
SW.14
SW.13
SW.12
SW.11
SW.10
SW.9
SW.8
Name
TxPDO Toggle
TxPDO State
Sync error
-
-
-
-
-
Bit
SW.7
SW.6
SW.5
SW.4
SW.3
SW.2
SW.1
SW.0
Name
-
ERROR
Limit 2
Limit 1
Overrange
Underrange
Key
Bit
Name
Description
SW.15
TxPDO Toggle
1
bin
Toggles with each new analog process value
SW.14
TxPDO State
1
bin
TRUE in the case of an internal error
SW.13
Sync error
1
bin
TRUE (DC mode): a synchronization error occurred in the expired cycle.
SW.6
ERROR
1
bin
General error bit, is set together with overrange and underrange
SW.5
Limit 2
1
bin
0: Limit function is not active
1: Value < Limit value in Index 0x08n0:13
2: Value > Limit value in Index 0x08n0:13
3: Value = Limit value in Index 0x08n0:13
SW.4
1
bin
SW.3
Limit 1
1
bin
0: Limit function is not active
1: Value < Limit value in Index 0x08n0:14
2: Value > Limit value in Index 0x08n0:14
3: Value = Limit value in Index 0x08n0:14
SW.2
1
bin
SW.1
Overrange
1
bin
Analog input signal lies above the upper permissible threshold for this terminal
SW.0
Underrange
1
bin
Analog input signal lies under the lower permissible threshold for this terminal
Control word
The EPI3xxx/ERI3xxx boxes have no control word
5.3.3
Settings of the IO-Link devices
To find the basic settings of the devices for each port, right-click the port and select
Settings
.
A new tab
Portx:: Settings
opens
.
Fig. 66: Context menu - Settings