Commissioning/configuration of IO-Link master/device
EPI3xxx, ERI3xxx
56
Version: 1.2
5.3.1.2
2. Automatic scanning of the IO-Link ports
This part of the documentation describes the configuration of the physically available IO-Link devices in
TwinCAT.
During automatic scanning of the IO-Link ports, the steps
WakeUp pulse, Baud rate setting, Reading of the
communication parameters,
plus
Parameter server
and
Cyclic data exchange
, if applicable, are performed,
Establishing the IO-Link communication [
. The corresponding IO-Link device must be connected to
the IO-Link port for this.
The connected devices are automatically detected and configured and a search is performed for the
associated IODD.
Finding connected IO-Link devices
The connected IO-Link devices can be found by clicking the
Scan devices
button (see the following figure
(C)).
Fig. 57: Scan devices (C)
The information window lists the connected device for each of the four ports. Only port 2 of the master is
assigned an IO-Link device. Confirm with the
OK
button.
Fig. 58: Information
Scan devices
To be able to work with the devices, the button
Reload Devices
(F4) must be clicked.
Fig. 59: Button:
Reload Devices