![Beckhoff EP3204 Documentation Download Page 51](http://html1.mh-extra.com/html/beckhoff/ep3204/ep3204_documentation_2719256051.webp)
Commissioning/Configuration
EP3204 and EP3314
51
Version: 2.2
Index 8000: RTD Settings Ch.1
Index (hex) Name
Meaning
Data type
Flags
Default
8000:1A
Connection technol-
ogy
Connection technology:
UINT16
RW
0x0000 (0
dec
)
0
2-wire
1
3-wire
2
4-wire
3
No sensor connected (only supported by hardware
version 00):
This setting skips the whole measurement, thus
speeding up the data acquisition for the other chan-
nels. The green status LED of the respective chan-
nel remains lit. The error bit of a deactivated chan-
nel is canceled and no longer set.
8000:1B
Wire calibration 1/32
Ohm
Only for 2-wire measurements:
contains the resistance of the supply line for the tempera-
ture sensor (in 1/32 ohm).
INT16
RW
0x0000 (0
dec
)
Index 8010: RTD Settings Ch.2
Index (hex) Name
Meaning
Data type
Flags
Default
8010:0
RTD Settings Ch.2
Maximum subindex
UINT8
RO
0x1B (27
dec
)
8010:01
Enable user scale
Activates user scaling
BOOLEAN
RW
0x00 (0
dec
)
8010:02
Presentation
Presentation of the measured value
BIT3
RW
0x00 (0
dec
)
0
Signed, in two's complement
1
Most significant bit as sign
2
High-resolution (1/100 °C steps)
8010:05
Siemens bits
The S5 bits are displayed in the three low-order bits
BOOLEAN
RW
0x00 (0
dec
)
8010:06
Enable filter
Enable filter, which makes PLC-cycle-synchronous data
exchange unnecessary
BOOLEAN
RW
0x00 (0
dec
)
8010:07
Enable limit 1
Activates limit check for limit 1
BOOLEAN
RW
0x00 (0
dec
)
8010:08
Enable limit 2
Activates limit check for limit 2
BOOLEAN
RW
0x00 (0
dec
)
8010:0A
Enable user calibra-
tion
Activates user calibration
BOOLEAN
RW
0x00 (0
dec
)
8010:0B
Enable vendor cali-
bration
Activates manufacturer calibration
BOOLEAN
RW
0x01 (1
dec
)
8010:0E
Swap limit bits
Swaps the two limit bits, in order to achieve compatibility
with older hardware versions.
BOOLEAN
RW
0x00 (0
dec
)
8010:11
User scale offset
User scaling offset
INT16
RW
0x0000 (0
dec
)
8010:12
User scale gain
Gain of the user scaling
INT32
RW
0x00010000
(65536
dec
)
8010:13
Limit 1
Value for limit 1
INT16
RW
0x0000 (0
dec
)
8010:14
Limit 2
Value for limit 2
INT16
RW
0x0000 (0
dec
)
8010:15
Filter settings
Filter settings
UINT16
RW
0x0000 (0
dec
)
0
50 Hz
1
60 Hz
2
100 Hz
3
500 Hz
4
1 kHz,
5
2 kHz
6
3.75 kHz
7
7.5 kHz
8
15 kHz
9
30 kHz
10
5 Hz
11
10 Hz
8010:16
Calibration interval
reserved
UINT16
RW
0x0000 (0
dec
)
8010:17
User calibration offset User calibration offset
INT16
RW
0x0000 (0
dec
)
8010:18
User calibration gain
Gain of the user calibration
UINT16
RW
0x4000
(16384
dec
)
Summary of Contents for EP3204