Product overview
EP1xxx
29
Version: 2.5.0
2.8.2
EP1816-0008 - Technical Data
Technical data
EP1816-0008
Fieldbus
EtherCAT
Fieldbus connection
2 x M8 socket (green)
Number of inputs
16
25 pin SUB-D socket
Nominal input voltage
24 V
DC
(-15%/+20%)
Input filter
10 µs
"0" signal voltage
-3...+5 V (EN 61131-2, Type 3)
"1" signal voltage
+11...+30 V (EN 61131-2, Type 3)
Input current
typically 3 mA (EN 61131-2, Type 3)
Module electronic supply
derived from control voltage Us
Module electronic current consumption
typically 120 mA
Sensor supply
derived from control voltage Us
Sensor current consumption
max. 0.5 A total, short-circuit proof
Power supply connection
Feed: 1 x M8 plug, 4-pin
Onward connection: 1 x M8 socket, 4-pin
Process image
16 input bits
Electrical isolation
Control voltage/fieldbus: yes
Permissible ambient temperature during operation
-25°C ... +60°C
0°C ... +55°C (according to cULus, see UL
Requirements)
Permissible ambient temperature during storage
-40°C ... +85°C
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC resistance/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP65, IP66, IP67 (conforms to EN 60529)
Installation position
variable
Approvals
CE, cULus
2.8.3
EP1816-0008 - Status-LEDs
Fig. 18: EP1816-0008 - Status-LEDs