Product overview
EP1xxx
26
Version: 2.5.0
2.7.3
EP1809, EP1819 - Technical data
Technical data
EP1809-0021
EP1809-0022
EP1819-0021
EP1819-0022
Fieldbus
EtherCAT
Fieldbus connection
2 x M8 socket (green)
Number of inputs
16
Input connections
M8
M12
M8
M12
Nominal input voltage
24 V
DC
(-15%/+20%)
Input filter
3 ms
3 ms
10 µs
10 µs
"0" signal voltage
-3...+5 V (similar to EN 61131-2, Type 3)
"1" signal voltage
+11...+30 V (similar to EN 61131-2, Type 3)
Input current
typically 3 mA (similar to EN 61131-2, Type 3)
Module electronic supply
derived from control voltage Us
Module electronic current
consumption
typically 130 mA (without sensor current)
Sensor supply
derived from control voltage Us
Sensor current consumption
max. 0.5 A total, short-circuit proof
Power supply connection
Feed: 1 x M8 plug, 4-pin
Onward connection: 1 x M8 socket, 4-pin
Process image
16 input bits
Electrical isolation
Control voltage / fieldbus: yes
Permissible ambient temperature
during operation
-25°C ... +60°C
-25°C ... +60°C
0°C ... +55°C
(according to
cULus, see UL
Requirements)
-25°C ... +60°C
-25°C ... +60°C
Permissible ambient temperature
during storage
-40°C ... +85°C
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC resistance / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP65, IP66, IP67 (conforms to EN 60529)
Installation position
variable
Approvals
CE
CE, cULus
CE
CE