Product overview
EP1xxx
20
Version: 2.5.0
2.5.2
EP1111-0000 - Technical Data
Technical data
EP1111-0000
Fieldbus
EtherCAT
Fieldbus connection
2 x M8 socket (green)
Task within EtherCAT system
identification of any EtherCAT group in the EtherCAT
network
Number of ID switches
3
Positions per ID switch
10
Number of different IDs
999
Module electronic supply
derived from control voltage Us
Module electronic current consumption
typically 120 mA
Power supply connection
Feed: 1 x M8 plug, 4-pin
Onward connection: 1 x M8 socket, 4-pin
Process image
2 byte input data
Weight
app. 165 g
Permissible ambient temperature during operation
-25°C ... +60°C
0°C…+55°C (according to cULus, see
Permissible ambient temperature during storage
-40°C ... +85°C
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC resistance/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP65, IP66, IP67 (conforms to EN 60529)
Installation position
variable
Approvals
CE, cULus
2.5.3
EP1111-0000 - Process image
ID inputs
You will find input data of the ID switches under under
ID Inputs
.
Fig. 11: EP1111-0000, ID inputs