Product overview
ELX3152 and ELX3158
14
Version: 2.0.0
2.3
Technical data
Technical data
ELX3152-0000
ELX3158-0000
Technology
intrinsically safe sensors
Number of inputs
2 (single ended)
8 (single ended)
Connection technology
2-wire, 3-wire
2-wire
Nominal voltage
24 V
DC
Signal current
0/4…20 mA
4…20 mA
Technical measuring range
107%*
Resolution
16 bit (incl. sign)
Measuring error
< ±0.3% (relative to full scale value)
Measuring resistance
typically 100 Ω
Input filter limit frequency
5 kHz
Conversion time
typically 1 ms
Supply voltage electronics
via E-Bus (5 V
DC
) and Power Contacts (24 V
DC
Ex, feeding by
ELX9560)
Current consumption from the E-Bus
typically 85 mA
typically 75 mA
Current consumption from Power Contacts
(ELX9560 power supply)
typically 10 mA + load
Electrical isolation
1500 V (E-Bus / field voltage)
Configuration
no address or configuration settings required
Distributed Clocks
yes
Bit width in the
process image
standard PDO (default) 2 x 4 byte
8 x 4 byte
compact PDO
2 x 2 byte
8 x 2 byte
Special features
standard and compact process image, activatable FIR/IIR filters,
limit value monitoring, NE43 NAMUR
Weight
app. 60 g
Permissible ambient temperature range
during operation
-25°C ... + 60°C
Permissible ambient temperature range
during storage
-40°C ... + 85°C
Permissible relative humidity
95%, no condensation
Permissible air pressure
(operation, storage, transport)
800 hPa to 1100 hPa
(this corresponds to a height of approx. -690 m to 2000 m over
sea level assuming an international standard atmosphere)
Dimensions (W x H x D)
app. 15 mm x 100 mm x 70 mm
(width aligned: 12 mm)
app. 27 mm x 100 mm x 70 mm
(width aligned: 24 mm)
Mounting
on 35 mm mounting rail conforms to EN 60715
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protect. class
IP20
Permissible installation position
Installation position and minimum distances [
Markings / Approvals
CE, UL, ATEX, IECEx, cFMus
CE, ATEX, IECEx
*) With a technical measuring range of 107% of the nominal range, the terminal also supports commissioning
with sensor values in the limit range and an evaluation according to NAMUR NE43.