Commissioning
EL922x
115
Version: 1.0
7.6.1
EL9221-xxxx
7.6.1.1
Restore object
Index 1011 Restore default parameters
Index
(hex)
Name
Meaning
Data type
Flags Default
1011:0
Restore default parame-
ters
Restore default parameters
UINT8
RO
0x01 (1
dec
)
1011:01
SubIndex 001
If this object is set to "
0x64616F6C"
in the set value dia-
log, all backup objects are reset to their delivery state.
UINT32
RW
0x00000000 (0
dec
)
7.6.1.2
Configuration data
Index 8000 Settings
Index (hex) Name
Meaning
Data type
Flags
Default
8000:0
Settings
Max. Subindex
UINT8
RO
0x19 (25
dec
)
8000:11
Nominal current
Nominal current (set fuse value), I
N
UINT8
RW
(0x80nF:17)
8000:19
Switch Programming
Control
LED button programming option: Indicated whether
the nominal current of programmable terminals can
be programmed via the LED button.
Disable
: Locked and not allowed. Only one query of
the nominal current is possible!
Enable
: Programming possible
UINT8
RW
---
Index 8010 DIG Safe State Active
Index
(hex)
Name
Meaning
Data type
Flags Default value
8010:0
DIG Safe State
Active
Maximum subindex
UINT8
RO
0x01 (1
dec
)
8010:01
Active
Enabling of the output state defined in
index 0x8011:01 in case of a bus error
0: output retains its current state.
1: output is switched to the state defined in
index 0x80n1.
BOOLEAN RW
0x01 (1
dec
)
Index 8011 DIG Safe State Value
Index
(hex)
Name
Meaning
Data type
Flags Default value
8011:0
DIG Safe State
Value
Maximum subindex
UINT8
RO
0x01 (1
dec
)
8011:01
Value
Defines the state of the output in case of a
bus error:
0: output off
1: output on
BOOLEAN RW
0x00 (0
dec
)