Mounting and wiring
EL6692
36
Version: 3.2
• Pull (4) the terminal module away from the mounting surface.
Avoid canting of the module; you should stabilize the module with the other hand, if required.
4.4
Positioning of passive Terminals
Hint for positioning of passive terminals in the bus terminal block
EtherCAT Terminals (ELxxxx / ESxxxx), which do not take an active part in data transfer within the
bus terminal block are so called passive terminals. The passive terminals have no current consump-
tion out of the E-Bus.
To ensure an optimal data transfer, you must not directly string together more than 2 passive termi-
nals!
Examples for positioning of passive terminals (highlighted)
Fig. 24: Correct positioning