Error handling and diagnostics
EL3632
186
Version: 2.8
6
Error handling and diagnostics
6.1
Error descriptions and troubleshooting
Error Codes
Error
Index
Underange
Index
Overrange
Index
TxPDO State
Index
Sync Error
Index
Error description
Remedy
1
1
Measurement is be-
low range
Reduce the input level,
change the gain (filter
settings)
1
1
Measuring range
exceeded
Reduce the input level,
change the gain (filter
settings)
1
General measuring
error
e.g. open circuit
1
Synchronization er-
ror
Jitter of master too high,
distributed clocks
switched off
The error LED lights up only in case of open circuit.
Troubleshooting
The dialog for setting the sampling rate is missing
The dialog for setting the sampling rate is missing. The TwinCAT System Manager uses the “online
description” of the terminal. The note to use the dialog for the parameterization is only available in the XML
description.
Solution: Make sure that the latest
is used.
The amplitude is too small
Filter settings incorrect.
Solution: Correct the settings in the CoE in the entries
The terminal switches to SAFEOP
The terminal switches to SAFEOP. The real-time-settings are not accurate enough.
Solution: Use a PC without mobile chipset/CPU.