![Beckhoff EK9500 Documentation Download Page 36](http://html1.mh-extra.com/html/beckhoff/ek9500/ek9500_documentation_2719251036.webp)
Configuration
EK9500
36
Version: 1.0.0
Select User Confirmation or Automatic Confirmation. Default Setting: User Confirmation
• Ebus Fallback mode
How the Coupler responds to a break in EtherCAT.
Set to Zero, Freeze, Stop Ebus. Default Setting: Set to Zero
• FBus Fallback Mode
How the Coupler responds to a break in the FBus.
Set to Zero, Freeze, Stop Ebus. Default Setting: Set to Zero
• TCP Timeout
Maximum time allowed for Ethernet Connection. Default Setting 30 Seconds
• Unicast TTL (Time To Live)
Used to determine if an Ethernet/IP Frame has been in the network too long and should be discarded
Default Setting 128 Seconds
• Unicast UDP Checksum
Enable/Disable UDP Checksum – Unicast (Frames sent to Single Destination). Checksum is a digit
representing the sum of the transmitted data used for error checking.
• Multicast TTL (Time to Live)
Used to determine if an Ethernet/IP Frame has been in the network too long and should be discarded
Default Setting 1 Second
• Multicast UDP Checksum
Enable/Disable UDP Checksum – Multicast (Copies of Frames sent to Multiple Destinations). Checksum is a
digit representing the sum of the transmitted data used for error checking.
Ethernet Statistics
Fig. 29: EtherNet Statistics
Ethernet Rx Frames: Received Frames
Ethernet Tx Frames: Transmitted Frames