Configuration
EK9500
30
Version: 1.0.0
5
Configuration
5.1
Configuration via the HTML pages of the Bus Coupler
An HTML page is available for the configuration. This can be reached via the IP address/Config
(e.g.192.168.1.3/Config). We recommend the use of Chrome or Firefox as browser.
If DHCP is used, enter the name of the Bus Coupler instead of the IP address. The default name of the Bus
Coupler starts with the string "EK-", followed by the last 3 bytes of its MAC address (MAC ID). The MAC
address can be found on the sticker on the left of the Bus Coupler.
Sample: The MAC address is 00-01-05-02-03-04. The resulting default name is "EK-020304". Now enter
"EK-020304/Config" in your browser. The login name is "guest", the default password is "1" (without quotes).
The firmware and hardware versions as well as the serial number can be read on the information diagnostic
page. The diagnosis history can be read if problems occur. The diagnosis history is not saved and is cleared
in the case of a restart.
Fig. 22: Configuration via HTML pages - information diagnostic page
Boot Opt
The Boot Opt allows you to enable/disable Remote Display. You can also restore the factory settings and
trigger a manual reboot of the device.
Fig. 23: Configuration via HTML pages – Boot Options