Product overview
CX20x0
15
Version: 2.5
Table 2: Available optional interfaces for the CX20x0.
CX20x0-xxxx Optional interfaces
CX20x0-N010 DVI-D, additional DVI-D socket for clone and extended display mode.
CX20x0-N011 DisplayPort, additional DisplayPort for clone and extended display mode
CX20x0-N030 RS232, D-sub connector, 9-pin.
CX20x0-N031 RS422/RS485, D-sub socket, 9-pin.
CX20x0-B110 EtherCAT slave, EtherCAT IN and OUT (2 x RJ45).
CX20x0-M310 PROFIBUS master, D-sub socket, 9-pin.
CX20x0-B310 PROFIBUS slave, D-sub socket, 9-pin.
CX20x0-M510 CANopen master, D-sub connector, 9-pin.
CX20x0-B510 CANopen slave, D-sub connector, 9-pin.
CX20x0-M930 PROFINET RT, controller, Ethernet (2 x RJ-45).
CX20x0-B930 PROFINET RT, device, Ethernet (2 x RJ-45 switch).
CX2100 power supply units
The CX2100 power supply units serve the basic CPU module and all additional modules. Bus Terminals (K-
bus) or EtherCAT Terminals (E-bus) can be attached on the right-hand side of the power supply units. The
power supply units are available in four different versions:
• CX2100-0004: E-bus/K-bus power supply unit with automatic switchover.
• CX2100-0014: E-bus/K-bus power supply unit with automatic switchover and passive ventilation.
• CX2100-0904: E-bus/K-bus power supply unit with automatic switchover and integrated capacitive
UPS.
• CX2100-0914: E-bus/K-bus power supply unit with automatic switchover and integrated electronic
charging unit for an external battery pack.
All power supply units feature an illuminated anti-glare LC display with two rows of 16 characters each for
displaying status messages. Application-specific texts can be displayed with the aid of user programs.
System, fieldbus and extension modules
System or fieldbus modules of type CX2500-xxxx can be connected on the left-hand side of the basic CPU
module. Up to four modules can be connected to the multi-pin connection on the left. Extension modules of
type CX2550 can be connected on the right between the basic CPU module and the power supply unit.
CX2900 battery pack
The battery pack is a charge store for the CX2000 product family and used as UPS in conjunction with the
CX2100-0914 power supply unit. In the event of a power failure the battery pack supplies the basic CPU
module and further devices (e.g. a Panel) via the CX2100-0914 power supply unit.
Software
In combination with the TwinCAT automation software, the CX20x0 Embedded PC becomes a powerful IEC
61131-3 PLC with up to four user tasks. In conjunction with EtherCAT and TwinCAT, it is possible to
implement very fast control processes in the microsecond range (XFC eXtreme Fast Control Technology).
It is also possible to execute Motion Control tasks with potentially up to 256 axes. Depending on the required
sampling time, several servo axes can be controlled. Even special functions such as flying saw, electronic
gearbox and cam plate can be realized.
In addition to handling real-time control tasks the TwinCAT real-time kernel leaves enough time for the user
interface (HMI). The high performance of the graphics core integrated in the CPU enables demanding
visualizations with advanced user interfaces to be realized.