Product overview
CX1500-M510, CX1500-B510
88
Version: 1.0
dec
hex
Telegram
type
dec
hex
Telegram
type
dec
hex
Telegram
type
873
369
RxPDO7*,
Nd.41
1429
595
SDO Tx
Nd.21
2.3.7
Emergency Object
In order to be able to inform other participating devices on the CANopen bus about internal device errors or
CAN bus errors, CANopen Bus Couplers can make use of the emergency object. It has a high priority, and
provides valuable information about the state of the device and of the network.
NOTE
Warning It is strongly recommended that emergency objects are evaluated - they provide a valuable source
of information.
Structure of the emergency message
The emergency object is always 8 bytes long; it contains first the 2-byte error code, then the 1-byte error
register, and finally the additional code of 5 bytes. This is divided into a 2-byte bit field and a 3-byte
parameter field:
11 bit
identifier
8 bytes of user data
0x80
(=128dec)
+ node-ID
EC0
EC1
EReg
Bit field 0:
Comm
Bit field 1:
DevErr
EMCY
Trigger
Info 0
Info 1