Page 2: ......
Page 3: ...1 UPS OCT LED 17 3 4 2 PWR LED 18 3 4 3 HDD LED 18 3 4 4 TC LED 18 3 5 Name plate 19 3 6 1 second UPS 20 4 Commissioning 21 4 1 Transport and unpacking 21 4 2 Installation in the control cabinet 22 4...
Page 4: ...Table of contents C6027 4 Version 1 1 8 Troubleshooting 41 9 Technical data 42 10 Appendix 43 10 1 Service and support 43 10 2 Approvals 44...
Page 5: ...rations depicted may deviate from the standard Trademarks Beckhoff TwinCAT TwinCAT BSD TC BSD EtherCAT EtherCAT G EtherCAT G10 EtherCAT P Safety over EtherCAT TwinSAFE XFC XTS and XPlanar are register...
Page 6: ...th or serious injuries WARNING Disregarding the safety notice may lead to death or serious injuries CAUTION Disregarding the safety notice may lead to minor injuries Warning of damage to property NOTE...
Page 7: ...of power consumption and power dissipation please refer to the respective data sheet Ensure that only trained specialists with a control and automation engineering background operate the Industrial P...
Page 8: ...rks The latter should be connected to the corporate network or the Internet only if appropriate protective measures have been set up In addition the recommendations from Beckhoff regarding appropriate...
Page 9: ...o the available processors the Industrial PC can be used for the following applications among others diverse automation and visualization tasks wide range of IoT tasks with data preprocessing complica...
Page 10: ...Protective conductor connection PE Low resistance protective earthing and functional earthing of the Industrial PC 4 Name plate Information on the equipment of the Industrial PC 5 Side cover Access to...
Page 11: ...Voltage socket pin numbering Table 2 Voltage socket pin assignment Pin Signal Description 1 ON PC_ON input 2 P S Power status output 3 GND 0 V 4 24 V Power supply The plug for the power supply is spec...
Page 12: ...llows based on the device generation Table 3 Controller classification based on device generation Device generation Controller C6027 0000 Intel i219 PHY for LAN1 and Intel i210 MAC PHY for LAN2 and LA...
Page 13: ...nically fused All ports are protected by a common overcurrent protection overcurrent detection All ports will be switched off if overcurrent occurs at any of the ports 1 2 3 4 4 3 2 1 1 2 3 4 4 3 2 1...
Page 14: ...rt signals are led out via the interface by default With the use of a level shifter cable the board switches the DisplayPort specification automatically to HDMI signals 1 2 19 20 X105 Fig 5 C6027_Disp...
Page 15: ...ering options are available 6x Ethernet adapter with 100 1000BASE T connection order designation C9900 E318 Any interfaces that are ordered are installed ex factory They extend the connection area at...
Page 16: ...e Intel i210 MAC PHY is used as the controller for all six ports 1 8 1 1 8 8 1 8 1 1 8 8 Fig 7 C6027_Optional Ethernet interfaces pin numbering Table 7 Ethernet interface pin assignment Pin Signal Des...
Page 17: ...he transmission quality of the UPS OCT signals UPS stands for the uninterruptible power supply One cable technology OCT enables the communication between PC and UPS to be transmitted together with the...
Page 18: ...arting start sequence is being run through Magenta Flashing 0 5 s S UPS capacitance test if S UPS exists Red magenta Flashing Checksum error during the I2C transmission in the bootloader Cyan Flashing...
Page 19: ...e last four digits indicate the product variant 3 Serial number BTN 4 UPS OCT LED 5 Date of manufacture 6 Power LED 7 Mainboard 8 CPU 9 Hard disk LED 10 Main memory 11 Storage medium 12 TwinCAT LED 13...
Page 20: ...S under the order designation C9900 U334 The capacitive 1 second UPS continues to supply the processor with power if the power supply fails During this period persistent data can be saved which are av...
Page 21: ...Industrial PC in particular the original packaging can improve the vibration resistance during transport NOTE Hardware damage due to condensation Unfavorable weather conditions during transport can c...
Page 22: ...the Industrial PC with four Torx TX10 screws and a tightening torque of approx 0 5 Nm Mounting plate 3 at the rear of the Industrial PC with two Torx TX10 screws and a tightening torque of approx 0 5...
Page 23: ...ndustrial PC according to the desired cable routing in the control cabinet In the case of mounting plates 1 and 3 the device can only be mounted via the rear panel in the control cabinet see fig 12 1...
Page 24: ...ounting plate 1 91 2 1 45 1 27 4 2 1 36 7 1 4 5 69 3 20 40 Fig 14 C6027 _mounting plate rear panel Fig 15 shows the dimensions using the mounting option with the connections pointing to the right with...
Page 25: ...ons 24 You need M4 screws for mounting After you have drilled the holes for the fastening screws in the control cabinet you can mount the Industrial PC in the control cabinet with mounting plates 1 or...
Page 26: ...e of the adapter into the DIN rail A 2 Push the device upwards so that the spring contacts of the adapter are pressed in B 3 Keep the device pressed upwards and also hook the upper side of the adapter...
Page 27: ...perating the device The cabling of the Industrial PC in the control cabinet must be done in accordance with the standard EN 60204 1 2006 PELV Protective Extra Low Voltage The PE conductor protective e...
Page 28: ...PC and thus avoid dangerous touch voltages EMC NOTE Hardware damage due to electromagnetic interference Using the Industrial PC without functional earthing can lead to hardware damage due to electroma...
Page 29: ...trial PC 28 and then plug in all data transfer cables Connecting the power supply Cables with a maximum cable cross section of 1 5 mm2 can be used for connecting the power supply For long supply lines...
Page 30: ...is shut down can lead to data loss Quit the running software and shut down the operating system before switching off the PC When the system is switched off or disconnected from its own power supply t...
Page 31: ...using the Beckhoff Device Manager to remotely configure the Industrial PC via a web browser More detailed information is available in the Beckhoff Device Manager manual First start Beckhoff Device Man...
Page 32: ...passwords are an important prerequisite for a secure system Beckhoff supplies the device images with standard user names and standard passwords for the operating system It is imperative that you chang...
Page 33: ...hock Never disconnect the cables from the device during thunderstorms Before you remove the Industrial PC from the control cabinet you must follow the following steps 1 Shut down the operating system...
Page 34: ...e PC until the fastening screws slide into the keyholes see Fig 23 3 Remove the PC from the control cabinet You have successfully disassembled the PC Fig 23 C6027 _Position of the fastening screws Dis...
Page 35: ...Dispose of the components in the following way Send plastic parts polycarbonate polyamide PA6 6 for plastics recycling Take metal parts to the metal recycling collection point Electronic parts such as...
Page 36: ...and the replacement of other device components contribute to this Repair Only the manufacturer may repair the device If a repair should be necessary contact Beckhoff Service see Chapter 10 1 Service...
Page 37: ...ponents Component Recommendation for replacement intervals years UPS battery pack 5 years 2 5 inch hard disk 5 years or after 20 000 operating hours at more than 40 C or after 30 000 operating hours a...
Page 38: ...n body by touching grounded metal e g control cabinet door Wear a wrist grounding strap Only remove new electronic components from the ESD packaging tinted plastic bag after putting on the wrist groun...
Page 39: ...should only be obtained from Beckhoff Service see Chapter 10 1 Service and support Table 15 Technical data of the battery Battery type Electrical properties at 20 C Dimensions Nominal voltage Nominal...
Page 40: ...h are designed for a particularly long data preservation For more information on the function of the BST please refer to the corresponding documentation If your storage medium is defective and there i...
Page 41: ...PC Other cause Check the power supply cable Call Beckhoff Service The Industrial PC does not boot fully Setup settings are incorrect Other cause Check the setup settings Call Beckhoff Service Computer...
Page 42: ...n EN 60068 2 6 10 to 58 Hz 0 035 mm 58 to 500 Hz 0 5 G approx 5 m s2 Shock resistance shock EN 60068 2 27 5 G approx 50 m s2 duration 30 ms EMC interference immunity conforms to EN 61000 6 2 EMC inter...
Page 43: ...can be found on the name plate Beckhoff Support Support offers you comprehensive technical assistance helping you not only with the application of individual Beckhoff products but also with other wid...
Page 44: ...hese limits are designed to provide adequate protection against adverse interference if the device is used in a commercial environment This device generates uses and may emit radio frequency energy an...
Page 45: ...7 _Mounting options for mounting plate 2 23 Fig 14 C6027 _mounting plate rear panel 24 Fig 15 C6027 _Mounting plate side panel 24 Fig 16 C6027 _Mounting plate DIN rail adapter 24 Fig 17 C6027 _Mountin...
Page 46: ...Pin assignment of DisplayPort 14 Table 7 Ethernet interface pin assignment 16 Table 8 Meaning of the UPS OCT LED 17 Table 9 Meaning of the PWR LED 18 Table 10 Meaning of the HDD LED 18 Table 11 Meani...
Page 47: ......
Page 48: ...Beckhoff Automation GmbH Co KG H lshorstweg 20 33415 Verl Germany Phone 49 5246 9630 info beckhoff com www beckhoff com More Information www beckhoff com C6027...