background image

Product overview

2.7

Integration into TwinCAT

The brake module can be integrated in the TwinCAT
System Manager as a completely normal I/O device
(1) and is parameterized (3) with the TCDrive
Manager (2).

Power Management

Configuration in the TC Drive Manager

Pos.

Name

Pos.

Name

1

Power management

6

Activation / deactivation of the internal brake resistor

2

Mains voltage selection

7

External brake resistor parameter list

3

Phase monitoring (deactivate for single-phase mains)

8

0 = Deactivation of the external brake resistor 
(

not

 recommended) 

1 = Standard energy management with external 
brake resistor
2 = Energy management with external 
      brake resistor (standalone)

4

Delay time until the phase monitoring responds (acti-
vate if mains is unclean)

9

Enabling / disabling the fan of the external brake resis-
tor and setting the switching thresholds Switch on
Level: Percentage specification of the rated capacity
value of the external brake resistor.Switch on Temp.:
Max. temperature value for the external brake resistor
in "°C".

5

Internal brake resistor parameter list

2.8

Energy management

Intelligent energy management ensures that energy is distributed evenly to the DC links and the internal
brake resistors when devices are used commonly in the drive system. This reliably prevents the undesirable
permanent load of only one device.

2.8.1

DC link

The connected servomotors are supplied with energy from the DC link. It serves as an energy storage and
first needs to be charged up after switching the device on, before it can supply the servomotors. The DC link
is designed such that it can take up and store a certain degree of surplus energy from the motor (brake
energy) and subsequently supply the motor again with this stored energy. If the upper limit of the energy
storage is reached, the brake chopper feeds any further brake energy into the internal or external brake
resistor, where it is converted into heat; it is then no longer available for the further operation of the motor.
The voltage is taken and evaluated as the indicator for the current energy level of the DC link. As soon as
the brake resistors have also reached their energy limit, the error ‘FD4C, DC link – overvoltage’ appears and
the energy flow to and from the motor is interrupted, i.e. the motor makes uncontrolled movements.

In a drive system, the DC links of the individual devices are connected so that the energy level of all devices
is the same, regardless of which motor the brake energy is currently being fed back from. In many cases
these feedbacks do not happen at the same time, and 

without

 a DC link system, for example, a device

would be at the limit and would already have to "destroy" energy in a brake resistor, even though other
devices could still store energy in the DC link. In a DC link connection the energy could be stored, since the
DC link of all linked devices would be loaded first, before the energy in the brake resistors would be
converted to heat.

AX5000 Brake module AX5021

8

Version: 1.3

Summary of Contents for AX5021

Page 1: ...AX5000 Brake module AX5021 Documentation 1 3 2016 10 18 TDmlAX 5021 0000 0200 Version Date Order No ...

Page 2: ......

Page 3: ...ata 5 2 3 Mechanical data 5 2 4 General overview 6 2 5 Pin strip assignment of X51 and X52 6 2 6 Electrical connection example 7 2 7 Integration into TwinCAT 8 2 8 Energy management 8 2 8 1 DC link 8 2 8 2 Operation modes of the AX5021 9 2 8 3 Braking power diagnosis 10 AX5000 Brake module AX5021 3 Version 1 3 ...

Page 4: ...ption is only intended for the use of trained specialists in control and automation engineering who are familiar with the applicable national standards It is essential that the documentation and the following notes and explanations are followed when installing and commissioning the components It is the duty of the technical personnel to use the documentation published at the respective time of eac...

Page 5: ...cal data Electrcal data AX5021 int Resistance1 W 150 int Resistance2 W 14 000 ext Resistance min Ω 22 ext Resistance3 W 6 000 ext Resistance4 W max 32 000 Power loss P W max 250 Charging rate 24 VDC A 0 3 0 4 DC link capacity µF 705 1 Durability break power Prms 2 Peak break power Ppeak 3 Durability brake power Prms 4 Peak brake power Ppeak 2 3 Mechanical data The external dimensions of the brake ...

Page 6: ... Pin strip assignment of X51 and X52 No Name 1 T input of the temperature measurement sensor of the external brake resistor 2 T input of the temperature measurement sensor of the external brake resistor 3 PE protective conductor 4 F output to the fan controller of the external brake resistor 5 F output to the fan controller of the external brake resistor 6 PE protective conductor 7 B output to the...

Page 7: ...servo drive also releases the greatest brake energy Attention Damage to devices Please analyze your application The brake module should always be placed directly be side the servo drive that releases the greatest brake energy This rule should also be ap plied if several brake modules are used in a drive system Pos Name Pos Name 1 PC with TwinCAT and PLC 6 Patch cable 2 Output terminal 7 Control ca...

Page 8: ...y from the DC link It serves as an energy storage and first needs to be charged up after switching the device on before it can supply the servomotors The DC link is designed such that it can take up and store a certain degree of surplus energy from the motor brake energy and subsequently supply the motor again with this stored energy If the upper limit of the energy storage is reached the brake ch...

Page 9: ...n mode the capacity of the DC link of the brake module is reduced by approx 10 At 90 DC link load the brake chopper then directs the generated braking energy to the external brake resistor and when this has reached its capacity limit into the internal brake resistor In this case the brake energy is first fed into the brake module since the brake choppers in the other servo drives are only activate...

Page 10: ...red in IDNs P 0 0220 int brake resistor and P 0 0221 ext brake resistor The values can be reset by entering zero Duty cycle corresponds to 100 seconds The energy values are monitored at the specified intervals 100 ms 1 s 10 s 20 s 40 s and 100 s The values for 100 s correspond to the continuous output The maximum values should be approx 10 below the resistor limits P 0 0207 or P 0 0208 If a curren...

Reviews: