4.7.4
Digital I/O on the Master (X1)
Technical characteristics
—
Ground reference is
Digital
-GND (DGND, terminal X1/4,5)
—
The logic is dimensioned for +24V / 7mA (
PLC-compatible
)
—
H-level from +12...36V / 7mA, L-level from 0...7V / 0 mA
BTB/RTO: Relay output, max. 30V DC or 42V AC, 0.5A
ENABLE input
The output stage of the servo amplifier is activated by the enable signal
(terminal X1/3, input 24V,
active-high
).
In the inhibited state (low signal) the motor which is attached does not have any torque.
Ready-to-operate contact BTB/RTO
Operational readiness (terminals X1/1 and X1/2 ) is signalled via a
floating
relay contact.
The contact is
closed
when all servo amplifiers in the system are ready for operation.
This signal is
not
influenced by the enable signal, the I²t- limit, or the regen threshold.
All faults cause the BTB/RTO contact to open and the switch-off of the output
stage (if the BTB contact is open, the output stage is disabled -> no power). A list
of the error messages can be found on page 66.
AX2500 Installation Manual
49
Beckhoff
02/06
Interfaces
AX2500