background image

Instructions for Replacing Beckett 2N1R LWCO Sensor

Part No. 62075-001

PARTS LIST:

(1) 7600Pxx LWCO Sensor
(1)  1K ohm resistor - used for testing sensor

INSTRUCTIONS:

1.  Remove power from the AquaSmart control.
2.  Unplug the existing sensor from the connection 

under the display and remove the sensor from 

the well.  If the sensor is mounted remotely from 

the control, remove the well clip used for holding 

the sensor cable in place and save for use when 

installing the new sensor.

3.  Disconnect the green sensor wire from the bullet/

connector, pipe clamp or from the green screw on 

the AquaSmart control.

4.  Before inserting the new sensor, use an ohm meter 

to check the continuity of the LWCO circuit.

  Attach 

one of the meter probes to the connector, screw or 

wire to which the green sensor lead was attached.  The 

second probe should go to metal on the boiler vessel 

(not the boiler jacket).

5.  A good connection reading 5 ohms or less should be 

possible.  Check all connections in the LWCO wiring 

circuit for possible issues.  If the reading is above 10 

ohms, run a new ground wire from the green screw 

on the control case to the boiler vessel.  If a new wire 

is used, connect the green lead on the new sensor to 

the green screw when the new sensor is installed. 

The 

LWCO function will not operate properly without a 

good connection from the green sensor lead back 

to the boiler vessel. 

6.  Insert the replacement sensor into the well.  Make 

sure the sensor is fully seated.  You should feel a 

slight resistance when the sensor pin reaches the 

clip in the well.  Continue pushing until the sensor 

comes to a solid stop. If the sensor is remotely 

mounted, reinstall the clip used to hold the sensor 

cable securely in place.

                

No Pin

Engagement

Full Pin

Engagement

7.  Plug the main sensor cable into the connector under 

the display.

8.  Reconnect the green sensor lead to the bullet/

connector, pipe clamp or to the green screw on the 

AquaSmart control.   

9.  Restore power to the AquaSmart Control.  Allow the 

control to go through the start-up process.  Follow the 

Control Checkout Procedure in the AquaSmart manual 

to confirm proper operation of the control.  

Proper 

operation of the control must be confirmed before 

leaving the installation site.

STANDBY

                     WTR: 120F

Normal Display in Standby

Reviews: