com
.
tom
INDUSTRY 115 – Start-up Guide
The CTI 115 devices communicates with the
com.tom PORTAL via Ethernet and the existing
network infrastructure. The communication
mechanism has a low data volume and can be
integrated easily in the existing network infra-
structure.
Device may only be put into service and operated by qualified
personnel.
The device is designed for an installation on a 35 mm DIN Rail in
dry rooms.
The power supply must be a grounded circuit (PELV).
The power supply must be a limited power source according to
EN60950-1 cap. 2.5 or the device must be provided with an anti-
surge fuse of 2 A
Pin Assignment
Power Supply
FE
Functional earth
GND
Ground
VCC
24 VDC
Serial Interface
RS485
Pin A
A (- / Y)
Pin B
B (+ / Z)
Ethernet Interface
ETH 0
Green LED
Link indication
Yellow LED
Activity indication
ETH 1
Green LED
Link indication
Yellow LED
Activity indication
LEDs
P
Device is powered
A
PLC status
B
Portal status
Other Interfaces
micro SD card interface
micro SD memory card
Getting Started
Wire the com.tom device according to the technical data. Get
the
appropriate
Getting Started
documentation
at
http://www.com-tom.de/start and follow the steps described
there to put your device into operation.
Part Numbers
00571218 (WEB-PLC)
CTI 115.W
00571222 (WEB-PLC)
CTI 115.W Starter Kit
00571310 (CODESYS)
CTI 115.C
00571260 (CODESYS)
CTI 115.C Starter Kit
General Data
Size (W x L x H)
36,5 x 61,5 x 99 mm
Operating temperature
0 to 55 °C
Electrical shock
Class III
Protection rating
IP20
EMC emission
IEC 61000-6-3
EMC immunity
IEC 61000-6-2
Compliance
CE, RoHS
Electrical Data
Supply voltage
24 VDC (
15 %)
Active current
< 50 mA (without I/Os)
Scope of supply
1 Piece
CTI 115
1 Piece
microSD card
1 Piece
Connector 3-pin
1 Piece
Connector 2-pin
1 Piece
Label MAC-ID
1 Piece
Start-up Guide
Copyright © 2018 Beck IPC GmbH
http://www.com-tom.de