MX08 Multichannel Weighing System, Technical Manual, Rev. 2.5 Page 81 of 144
The meanings of the annunciater LEDs in operation are given below.
LED
Symbol Name
Pwr
Power
MX08 PN is not powered. Check power cable.
MX08 PN is powered.
Lnk
Link
No data transmission done.
Data transmission done to xFace or Modbus-RTU
Err
Error
No Error found.
Error: Look at the error table in Section 9.6.
Blank Light
Flash Blank for 0.3 second
Table 9.1 - Annunciater LEDs
MS Module Status LED
LED State
Description
Comment
Off
Not power or not initialized
No power or profinet module is
in initialization state
Green
Initialized
Green, 1 flash
Initialized, diagnostic event(s)
present
Diagnostic is active
Red
Exception error
There is an exception error
Red, 1 flash
Configuration Error
Check GSDML configuration
Red, 2 flashes
IP Address Error
IP address not set
Red, 3 flashes
Station Name Error
Station name not set
Red, 4 flashes
Internal Module Error
Re-energize the instrument.
If seen again, change the board.
LINK/Activity LED
LED State
Description
Comment
Off
No Link
No link, no communication
present
Green
Link
Ethernet link established, no
communication present
Green, flickering
Activity
Ethernet link established,
communication present