301: Eng head
overt SW
Engine head control temperature greater than 540 degrees C
AR
C
302: Eng head
t'couple diff
Magnitude of the difference between the engine head control and limit thermocouples is
greater than 100 degrees C
UR
C
303: Eng head
t'couple cont
Engine head control thermocouple failure
UR
C
304: Eng head
t'couple lim
Engine head limit thermocouple failure
UR
C
305: Eng under
current
Engine current less than 0.1A, 60 seconds after grid connection
SR
L
308: Stop
resistor integrity
The stop resister integrity check has failed
SR
M
309: Power fail
detection
Power failure detected
AR
F
310: Power mon
comm fail
No data received from the power meter IC in the last 10 seconds or the power monitor
failed to register with the EGC microcontroller within 10 seconds of power up
AR
F
311: EGC
comm. failure
Communication timeout or communication failure
AR
F
394: Eng BCU
com fail
Engine BCU comm. failure
ARP
F
395: Supp BCU
com fail
Supplementary BCU comm. failure
ARP
F
396: Eng head
control therm.
Engine head control thermocouple false reading
AR
C
397: Eng head
Limit therm.
Engine head safety thermocouple false reading
AR
C
398: Eng head
control rise
Engine head control thermocouple rise rate less than30 deg C in first min.
AR
C
399: Eng head
Limit rise
Engine head safety thermocouple rise rate less than30 deg C in first min
AR
C
400: Flow dir
heat gen
Return temperature > flow temperature for longer than 3 minutes
UR
UR
I
421: Eng bu exc
temp diff h'ex
Engine burner excessive temperature difference across the heat exchanger
AR
I
422: BCU Eng
bu inconsistent
Transmitted state of the engine burner BCU isn't consistent
AR
F
423: BCU Supp
bu inconsistent
Transmitted state of the supplementary burner BCU isn't consistent
AR
F
424: Rep. loss
of flame Eng bu
Repeated loss of flame engine burner
UR
E
425: Rep. loss
of flame Supp
bu
repeated loss of flame supplementary burner
UR
E
428: Boiler flow
Eng bu
Flow has been < 7 L/min for more than 30 minutes
AR
I
page 79
17.5 Exceptional conditions
1. In exceptional cases, the display will show an error screen see diagram below.
2. With the following information:
An error number
A short description of the error
The display may show a flashing spanner, a flame crossed out or both depending on the level of the error
3. Pressing the menu button will return the THINK Controller to the standard display which will now show the following symbol
which indicates that an error or fault has
occurred in the appliance. After 1 minute the display will automatically revert to the error screen.
4. Press the menu button twice to revert to the error display immediately. A list of error codes is shown in
This list contains both user reset and automatic
reset codes. Automatic codes are given here as they are capable of clearing automatically and do not necessarily indicate that a service visit is required.
Summary of Contents for ECOGEN 24/1.0
Page 69: ...Fig 77 Fig 78 Fig 79 page 69 16 0 Schematic Wiring 16 1 Burner Control Units BCU Connections...
Page 70: ...page 70 16 2 Milligrid 24 way Connector...
Page 71: ...page 71 16 3 14 way Connector...
Page 72: ...page 72 16 4 Engine Circuit...
Page 73: ...page 73 16 5 Power Monitoring 24Vdc Power Supply...
Page 74: ...page 74 16 6 External Connections External Wiring...
Page 85: ...page 87...
Page 86: ...page 88...
Page 87: ...page 89 Section P...
Page 88: ...page 90...
Page 89: ...page 91 Section Q Engine developing less than 950W after 15 minutes running at maximum rate...
Page 91: ...page 93 page 94 page 95 page 96 MICRO CHP SYSTEM COMMISSIONING CHECKLIST...
Page 92: ...page 97...