PD-TaD 80
Connecting the system
822-188-3
35 / 74
6.10 Connecting the system for PD measurement
6.10.1 Connecting the PD-TaD in the cable test van
Prerequisites
The workplace must be de-energised, earthed and short-circuited.
Further information: Chapter
Ensuring there is no voltage at the work place
(on page 32)
The connection points and far end are prepared for the measurement tasks.
Further information: Chapter
Preparing the test object terminals
(on page 32)
HV coupling unit of PD-TaD and the cable terminations of the test object are clean and
dry.
Further information: Chapter
Cleaning the PD-TaD 80 and system components
(on page
Required equipment
PD-TaD incl. connection cables
HF filter
PoE cable on hand cable drum
Anti-corona protection
Note:
All the necessary connection cables and connecting elements are included in the
standard delivery.
Procedure