Mounting steps
Manual Single Power Unit BUM64S/A/F
Document no.: 5.01056.03
Baumüller Nürnberg Electronic GmbH & Co. KG
32
5.2
5.2
Mounting steps
The mechanical mounting consists of the following steps:
m
select the switching cabinet.
m
produce the drill holes/threaded holes and the cut-out (variant A/F only).
m
mount the unit.
m
connect the coolant circulation (variant F only), test the tightness and perform a pres-
sure test.
Further information concerning the single steps are given in the following sections.
5.2.1
Select a switching cabinet
BUM64S/A/F units are build-in appliances with respect to EN 50178/VDE 0160
section 5.2.6. They are intended for mounting into ordinary switching cabinets, which
meet the minimum requirements regarding the protection class stated in EN 50178/VDE
0160, section 5.2.4 (IP 2X, eventually also IP4X acc. to EN 60529/5.1).
WARNING
The following
may occur
,
if you do not observe this warning information:
m
serious personal injury
m
death
The hazard is:
mechanical influence.
The units weigh depending on the model between 65
and 88 kilograms.
select a switching cabinet, which can carry this weight permanently
NOTE
If you mount a window variant (F/A), the back side may only have a maximum thickness of
6 mm.