Safety Functions
Operation Manual
Safety Module for b maXX 5000
BM5-O-SAF-002/3
Document no.: 5.11016.03
77
10
10.10.1Error reaction with function-specific SS1 time for the safety function "SLP"
With the software extension SAF-002/3 and with the SAF module configuration software
ProSafePara from version v1.1.0.0 onwards for every safety function a function-specific
SS1 time can be parameterized:
Figure 34:
P215.005: SS1 time for the safety function „SLP“
This time always acts as a delay if an individual error occurs.
This is supposed to allow the drive to drive down a brake ramp before the STO is
activated.
The following individual error can occur at the function "SLP":
m
Switchover to a data set which was not set
m
There is no encoder connected
m
Encoder standstill time extended
m
Homing was not carried out
m
Exceeding the tolerance window
If a value in P215.005 is parameterized greater than zero, STO is not immediately carried
out if an individual error occurs, but at first the parameterized time of this function is
processed. An automatic signalization to the controller is connected if the error occurs.
Thereby, the drive error 1066 "SS1 stop forced by SAF module" is initiated.
The related error reaction must be parameterized in the controller (refer to
"Parameterization of the error reaction" and SS1 Stop Time" in
).
Example:
During the process of the function "SLP" the individual error "Exceeding the position
range" occurs. In
on page 75 this case is shown. Thereby, the time period
"SS1" accords to the time parameterized in P215.005 before "STO" is carried out.