Installation
Operation Manual
b maXX safe PLC
BMC-M-SAF-02
Document no.: 5.07020.04
Baumüller Nürnberg GmbH
54
9.6
In order to be able to fulfil the EN 60 204-1 standard (electrical equipment of machines),
you will have to use the cables it recommends. The connection plugs must not be able to
fall out - otherwise, the danger of short circuits, external voltage, etc. will arise.
h
Make sure that the connection cable is routed in a EMC-compatible manner.
9.6.3
Safety-related connection technology
The b maXX safe PLC can be connected by means of the local I/O bus or by means of a
field bus with safety-oriented I/O terminals.
9.6.4
Requirements on the connection cable
Baumüller approves the following cables for use:
m
RS485 interface:
Stranded cables in pairs with a recommended cross-sectional area of 0.5 mm², PVC
outer jacked and overall shielding made of tin-plated mesh may be used.
Such as: Type LIYCY 6 x 2 x 0.14 mm²
m
RS232 interface:
Shielded cable with a recommended cross-sectional area of 0.5 mm².
Further information can be found in
CAUTION!
Special care is to be given to ensure that the electromechanical sensors (safety
switching devices) are supplied with suitable timing signals for short circuit recogni-
tion.
Electromechanical switches must meet the requirements of IEC 60947-5-1.
NOTICE!
Use 60°/75° copper cable if you are following UL 508 C
NOTICE!
The climatic properties namend in appendix
on page 110 are also valid for
the used cables.