103
Operation Manual
b maXX safe PLC
BMC-M-SAF-02
Document no.: 5.07020.04
A
PPENDIX
C - C
HECKLISTS
The use of checklists serves documentation purposes and guides in the implementation
of a safety system. The checklists reproduced in Appendix C - Checklists serve to prevent
errors and must be processed carefully for every project. It is also required to make cop-
ies of the printed checklists.
No claim is made that the checklists are complete. There may be additional requirements
depending on the specific plant.
C.1
Planning checklist
Seria
l no.
Requirement
Fulfilled
Remarks
Yes
No
1
Planning
1.1
Has a risk assessment been carried out
and have the required SIL and performance
levels in accordance with DIN EN ISO
13849-1 or IEC 62061 been determined?
1.2
Are power supplies according to PELV
specifications being used exclusively?
1.3
Is the line routing carried out in accordance
with the applicable standards and guide-
lines?
1.4
Is the electrical supply for the local I/O ter-
minals and field bus components properly
dimensioned?
1.5
Do all safety-oriented system components
meet the requirements of the established
SIL (IEC 61508), performance levels (DIN
EN ISO 13849-1) and safety category (DIN
EN 954-1)?