Configuration
Parameter manual
b maXX
BM5800
Document No.: 5.16029.03
Baumüller Nürnberg GmbH
134
3.4
3.4.5.7 Description of the parameter
171.1
Control word reluctance
171.3
Ld curve family
Nonlinear direct axis inductance depending on the currents Isd and Isq. The first index
shows the dependence of Id, the second of Iq.
171.12
Motor constant K
FLOAT
-1
1e9
-1
A
1:1
X
171.13
MTPF Table
FLOAT
-100
0
-100
%
1:1
X
171.14
Nominal flux
FLOAT
0.0001
1e9
1
Vs
1:1
X
171.15
State field weakening of
IPMSM
DINT
0
10
0
1:1
X
171.16
Total reference current
FLOAT
-10000
10000
0
A
1:1
X
171.17
Maximal torque current
from flux
FLOAT
0
10000
0
A
1:1
X
171.20
Magnetic flux
FLOAT
0.0001
1e9
0.1
Vs
1:1
X
171.21
State identification non-
linearity
UINT
0
0xFFFF
0
1:1
X
Bit no.
Meaning
0
Motor constant determined via Id
nom
and I
nom
1
Calculate motor constant via Lq, Ld and magnetic flux
4 … 2
Reserved
5
Start identification of Lq, Ld and magnetic flux
6
Start identification of the magnetic flux
8 ... 7
Reserved
9
Recalculation of the tables
13 ... 10
Reserved
14
Transfer of the inductances from autotuning and of the Ke factor from
motor type plate as constant values
15
Calculate MTPF table