Set Value Generators
Parameter manual
b maXX
BM3000
Document no.: 5.12001.07
Baumüller Nürnberg GmbH
414
4.6
m
change of set value from actual set value at ramp function generator output
to 0%. This causes a constant braking time from all speeds at ramp function generator
output.
For correct functioning of the braking procedures on the Quick Stop or Ramp-down
ramps, the speed controller must be adequately configured.
110.9
S-Curve ramp-up time
Rounding of the ramp corners on ramp-up for the speed-controlled operating modes. The
time selected here applies to a 100% set value change
The set S-Curve ramp-up time must be less than the set ramp-up time.
Total ramp-down time for a 100% set value change:
T
TotalRamp-upTime
= T
Ramp-upTime
+ T
SCRamp-upTime
110.10
S-Curve ramp-down time
Rounding of the ramp corners on ramp-down for the speed-controlled operating modes.
The time selected here applies to a 100% set value change
The set S-Curve ramp-down time must be less than the set ramp-down time.
Total ramp-down time for a 100% set value change:
T
TotalRamp-downTime
= T
Ramp-downTime
+ T
SCRamp-downTime
110.11
Smoothing
A PT
1
element is implemented to achieve rounding of the ramp corners. The time con-
stant of the PT
1
element can be adjusted using this parameter.
The smoothing is only effective if a trapezoidal profile is set for the ramp shape.
The smoothing is also active if the ramp times (
Ramp-down time) are set to zero.
110.12
Set value zone
This parameter defines the reporting threshold for the Ramp Function Generator Status
(Bit 12) "Set Value Reached".
The "Set Value Reached" status bit is set if the following is valid:
FG
Output
- HLG
Input
Set value zone