Actual value PID controller 1
Value of the actual value of the PID controller.
The source of this actual value can be selected in
„Axis index PID controller 1“.
If the source is not selected (
= 0) the actual value can be written via fieldbus or
an analogous input.
If the source is selected (
0) and the value of the source parameter is less than
the minimum value or greater than the maximum value of the actual value, the actual val-
ue is limited to its minimum or maximum value. This will be signalized in
bit 9.
150.15
Output PID controller 1
Value of the output of the PID controller.
The target of the output can be selected in
„Target number output PID controller
1“.
The output is set to 0 at deactivated PID controller.
150.16
Integral term PID controller 1
Display of the unlimited integral term of the PID controller.
The integral term is set to 0 permanently at deactivated PID controller or switched off in-
tegral controller.
150.17
Mode PID controller 2
Configuration of the PID controller 2 see
table.
150.18
Status PID controller 2
Status of the PID controller:
Bit
Meaning
0
0: PID controller is deactivated
1: PID controller is activated
3 ... 1
Reserved
4
1: PID controller output is limited
7 ... 5
Reserved