Configuration
Parameter manual
b maXX
BM3000
Document no.: 5.12001.07
Baumüller Nürnberg GmbH
184
4.4
106.22
Gain sine
Amplification of the sine signal. Automatically adjusted when optimization activated.
Can also be set as a fixed parameter.
106.23
Gain cosine
Amplification of the cosine signal. Automatically adjusted when optimization activated.
Can also be set as a fixed parameter.
106.24
Sine signal
Analog value of sine trace (after correction).
At square-wave incremental encoders the measuring value of the B trace is shown. How-
ever the displayed value is only usable up to approximately 18 kHz signal frequency.
106.25
Cosine signal
Analog value of cosine trace (after correction).
At square-wave incremental encoders the measuring value of the A trace is shown. How-
ever the displayed value is only usable up to approximately 18 kHz signal frequency.
106.43
Resolver mode
Via this mode the amplitude and the phase adjustment of the resolver can be automated
and the resolver frequency and the evaluation procedure can be set.
Bit
Meaning
0
0
: manual setting
1
: automatically amplitude setting
1
0
: manual setting
1
: automatically phase setting
3 ... 2
Reserved
4
Resolver frequency
0
: 7.8125 kHz without synchronization on the fieldbus
1
: 8 kHz with synchronization on the fieldbus