Commissioning BM25xx
Parameter manual
b maXX
BM3000
Document no.: 5.12001.07
17
2
2.2
Voltage test
2.3
Requirements for the electrical supply
For all important data, see the Operating Manual for the
b maXX
2500.
Small deviations in the electrical supply from the requirements can result in malfunctions
of the device. If the supply deviates greatly from the requirements, the device could be
destroyed.
The device may only be operated in environments of the second type (industrial environ-
ment).
The destruction of the device can cause personal injury.
DANGER!
Risk of fatal injury from electrical current!
During the routine test of these devices, a voltage test is performed by Baumüller
Nürnberg GmbH in accordance with EN 61800-5-1, Section 5.2.3.2. It is thus unnec-
essary for the customer to do this.
Therefore:
m
Subsequent tests of the devices using high voltages may only be performed by
Baumüller Nürnberg GmbH.
m
Disconnect the converter from the system during high-voltage testing!
DANGER!
Danger to life from electric current!
If the requirements for the electrical supply are not complied with, the device may be
damaged/destroyed and consequently present a significant danger to persons.
Therefore:
m
Before installation, make sure that the requirements for the electrical supply are
met.