![Baumuller b maXX BM1000 Manual Download Page 142](http://html.mh-extra.com/html/baumuller/b-maxx-bm1000/b-maxx-bm1000_manual_2711384142.webp)
Required environmental conditions
Manual
b maXX
®
BM1000
Document No. 5.07003.04
Baumüller Nürnberg GmbH
142
D.1
D.1
Required environmental conditions
D.2
Non-electrical data
1)
98/37/EG, appendix I, chapter 1.7.4.f, paragraph 8
Operation
Air Temperature:
-10 to +50 °C (14 to 122 °F)
-10 to +40 °C (14 to 104 °F)
for side-by-side mounting
Relative Humidity:
< 90 %, no condensation allowed
Atmospheric pressure:
86 to 106 kPa
Installation Site Altitude:
< 1000 m
Vibration:
< 20 Hz: 9.80 m/s
2
(1G) max
20 to 50 Hz: 5.88 m/s
2
(0.6 G) max
Storage
Transportation
Temperature:
-20 °C to +60 °C (-4 °F to 140 °F)
Relative Humidity:
< 90 %, no condensation allowed
Atmosphere pressure:
86 to 106 kPa
Vibration:
<20 Hz: 9.80 m/s
2
(1 G) max
20 to 50 Hz: 5.88 m/s
2
(0.6 G) max
Pollution Degree
2
suitable for a factory type environ-
ment.
NOTE
m
Operating, storing or transporting the
b maXX
®
BM1000
outside these conditions may
cause damage to the device.
m
Failure to observe these precautions may void the warranty!
Device
b maXX
®
BM1000
Dimensions
(W x H x D)
Weight with controller,
without plug-in modules
Noise
emission
Frame 1
72 x 142 x 152 mm
1.2 kg
max. 54 db(A)
1)
Frame 2
100 x 174 x 152 mm
1.9 kg
max. 54 db(A)
1)
Frame 3
130 x 260 x 170 mm
4.2 kg
max. 63 db(A)
1)
Summary of Contents for b maXX BM1000
Page 1: ...E 5 07003 04 Manual b maXX BM1000 Basic unit ...
Page 108: ...Manual b maXX BM1000 Document No 5 07003 04 Baumüller Nürnberg GmbH 108 of 174 ...
Page 118: ...Manual b maXX BM1000 Document No 5 07003 04 Baumüller Nürnberg GmbH 118 of 174 A ...
Page 172: ...Manual b maXX BM1000 Document No 5 07003 04 Baumüller Nürnberg GmbH 172 of 174 Index ...
Page 174: ...Manual b maXX BM1000 Document No 5 07003 04 Baumüller Nürnberg GmbH 174 of 174 Notes ...
Page 175: ......