![Baumuller b maXX BM1000 Manual Download Page 133](http://html.mh-extra.com/html/baumuller/b-maxx-bm1000/b-maxx-bm1000_manual_2711384133.webp)
Spare parts and accessories
Manual
b maXX
®
BM1000
Document No. 5.07003.04
133
B
B.5
Non-fuse circuit breaker
Per UL 508C, paragraph 45.8.4, part a:
m
For 1-phase drives, the current rating of the breaker shall be 4 times maximum input
current rating.
m
For 3-phase drives, the current rating of the breaker shall be 4 times maximum output
current rating.
(Refer to
from page 143 for rated input/output current)
B.6
Digital keypad
BM1-HMI-01-00-00
Figure 71:
Digital keypad
B.7
Digital keypad cable
1-phase
3-phase
Model
Recommended
non-fuse breaker [A]
Model
Recommended
non-fuse breaker [A]
BM1211
10
BM1412
5
BM1212
15
BM1413
5
BM1213
20
BM1414
10
BM1224
30
BM1425
15
BM1225
50
BM1426
20
BM1437
30
BM1438
40
BM1439
50
Model
Length
K-HMI-BM1-006
0.6 m
K-HMI-BM1-010
1.0 m
K-HMI-BM1-020
2.0 m
K-HMI-BM1-030
3.0 m
K-HMI-BM1-050
5.0 m
Summary of Contents for b maXX BM1000
Page 1: ...E 5 07003 04 Manual b maXX BM1000 Basic unit ...
Page 108: ...Manual b maXX BM1000 Document No 5 07003 04 Baumüller Nürnberg GmbH 108 of 174 ...
Page 118: ...Manual b maXX BM1000 Document No 5 07003 04 Baumüller Nürnberg GmbH 118 of 174 A ...
Page 172: ...Manual b maXX BM1000 Document No 5 07003 04 Baumüller Nürnberg GmbH 172 of 174 Index ...
Page 174: ...Manual b maXX BM1000 Document No 5 07003 04 Baumüller Nürnberg GmbH 174 of 174 Notes ...